Qualified Products Home
639-Electrical Power Service Assembly

A1 ) Service Disconnect - Heavy Duty Safety Switch (Main Disconnect)
NEMA Heavy Duty Type HD with NEMA 3R, outdoor enclosure (rainproof **); 60 Ampere, 120/240 Volt, Single Phase; Fusible, 2 Pole, 3-Wire; Replace with item “B” below when Traffic Infraction Detector (TID) equipment is connected to Main Disconnect; (Conformance with UL 98, Listed File E2875 or E154828; NEMA Standards Publication KS1, Enclosed Switches; Federal Specifications WS-865c for Type HD)
FDOT_APL_NOAPPROVALMANUFACTURERDEVICE_DESCRIPTION
N/A08/01/2009Cutler-Hammer (Eaton Corp.)DH222NRK/NEMA 3R
N/A08/01/2009General Electric Co. (GE)TH3222R/NEMA 3R
N/A09/22/2014Siemens Industry Inc.HF222NR/(Type 3R) Heavy Duty Safety Switch with Equipment Ground Lug Kit (HG61234) and Neutral Kit (HN623)
N/A08/01/2009Square D Comapny(Schneider Electric)H222 NRB/NEMA 3R

A2 ) Service Disconnect - (Same as A1) Exception**: with NEMA 4X Enclosure - (Required on FDOT Projects)
Raintight, watertight, corrosion resistant, windblown dustproof outdoor enclosure; Type 304 Stainless Steel (Conformance with UL 98, Listed File E2875 or E154828; NEMA Standards Publication KS1, Enclosed Switches; Federal Specifications WS-865c for Type HD).
FDOT_APL_NOAPPROVALMANUFACTURERDEVICE_DESCRIPTION
N/A01/27/2011Cutler-Hammer (Eaton Corp.)DH222NWK or DH262NWK/NEMA 4X
N/A01/27/2011General Electric Co. (GE)TH3222SS/NEMA 4/4X
N/A09/22/2014Siemens Industry Inc.HF222S/(Type 4X) Heavy Duty Safety Switch with Equipment Ground Lug Kit (HG61234) and Neutral Kit (HN623)
N/A01/27/2011Square D Comapny(Schneider Electric)H222 DS/NEMA 4/4X

B1 ) Service Disconnect - Heavy Duty Safety Switch (Main Disconnect Required with TID equipment):
NEMA Heavy Duty Type HD with NEMA 3R, outdoor enclosure (rainproof **); 60 Ampere, 120/240 Volt, Single Phase; Fusible, 3- Pole, 4- Wire; (Conformance with UL 98, Listed File E2875 or E154828; NEMA Standards Publication KS1, Enclosed Switches; Federal Specifications WS-865c for Type HD)
FDOT_APL_NOAPPROVALMANUFACTURERDEVICE_DESCRIPTION
N/A08/01/2009Cutler-Hammer (Eaton Corp.)DH322NRK/NEMA 3R
N/A08/01/2009General Electric Co. (GE)TH4322R/NEMA 3R
N/A09/22/2014Siemens Industry Inc.HF222NR/(Type 3R) Heavy Duty Safety Switch with Equipment Ground Lug Kit (HG61234) and Neutral Kit (HN623)
N/A08/01/2009Square D Comapny(Schneider Electric)H322 NRB/NEMA 3R

B2 ) Service Disconnect - (Same as B-1) Exception**: with NEMA 4X Enclosure - (Required on FDOT Projects)
Raintight, watertight, corrosion resistant, windblown dustproof outdoor enclosure; Type 304 Stainless Steel (Conformance with UL 98, Listed File E2875 or E154828; NEMA Standards Publication KS1, Enclosed Switches; Federal Specifications WS-865c for Type HD)
FDOT_APL_NOAPPROVALMANUFACTURERDEVICE_DESCRIPTION
N/A01/27/2011Cutler-Hammer (Eaton Corp.)DH322NWK or DH362NWK/NEMA 4X
N/A01/27/2011General Electric Co. (GE)TH4322SS/NEMA 4X
N/A09/22/2014Siemens Industry Inc.HF222S/(Type 4X) Heavy Duty Safety Switch with Equipment Ground Lug Kit (HG61234) and Neutral Kit (HN623)
N/A01/27/2011Square D Comapny(Schneider Electric)H322 DS/NEMA 4X

C ) 40 & 15 Amp Fuses for Service Disconnect - Heavy Duty Safety Switch
Dual-Element, Time-Delay Fuses [10 seconds (minimum) at 500% rated current]; 250 Volt; Interrupting Rating: 200,000A RMS Sym. DC Ratings: 20,000 A/C @ 125 VDC (UL Standard 248-12, Class RK-5, Guide JDDZ)
FDOT_APL_NOAPPROVALMANUFACTURERDEVICE_DESCRIPTION
N/A08/01/2009Cooper Bussman Inc.Fusetron FRN-R-15
N/A08/01/2009Cooper Bussman Inc.Fusetron FRN-R-40
N/A08/01/2009Ferraz ShawnutTri-Onic TR15R
N/A08/01/2009Ferraz ShawnutTri-Onic TR40R

D ) Outdoor Load Center (Secondary Disconnect Required for TID equipment): (Refer to Notes)
NEMA 3R outdoor, rainproof enclosure; Current Rating 100 Amps, Copper wire size #8-1 AWG; 120/240 VAC, Single Phase w/ 40 Amp, 2-pole, Main Circuit Breaker and 20 Amp, Single pole, Branch Circuit Breakers w/ AIR Rating 10Ka (Conformance with Federal Specification W-P-115c as Type 1 Class 2; UL and NEMA Standards)
FDOT_APL_NOAPPROVALMANUFACTURERDEVICE_DESCRIPTION
N/A01/25/2011Square D Comapny(Schneider Electric)QO6-12L100RB/Series G04

E ) Transient Protection Device
Also known as Surge Protective Devices (SPDs) or Surge Lightning Arrester is required for installation with all Service Disconnect switches; Rated for a maximum permissible line to ground voltage of 175 VAC; (Conformance with NEMA standards for surge arresters)
FDOT_APL_NOAPPROVALMANUFACTURERDEVICE_DESCRIPTION
N/A12/22/2011Intermatic Inc.AG2401C
N/A12/22/2011Square D Comapny(Schneider Electric)SDSA1175

NOTES: FDOT Traffic Infraction Detectors (TID) a.k.a. Red Light Running Camera System (RLRC) EQUIPMENT and MATERIALS FOR USE & OPERATION OF TRAFFIC INFRACTION DETECTOR EQUIPMENT QPL APPROVAL REQUIRED FOR DEVICES WHEN INSTALLED WITH PWWM TRAFFIC SIGNAL EQUIPMENT (NOTE: Equipment Owned, Operated and Maintained by the Traffic Infraction Detector Company)



Square D Comapny(Schneider Electric)www.squared.com
Siemens Industry Inc.w3.usa.siemens.com/powerdistribution/us/en/Pages/low-medium-voltage.aspx
Cooper Bussman Inc.www.bussmann.com
Intermatic Inc.www.intermatc.com
Cutler-Hammer (Eaton Corp.)www.eaton.com
General Electric Co. (GE)www.geindustrial.com
Ferraz Shawnutwww.ferrazshawnut.com

HISTORY:
Addition of Main and Secondary Disconnects for use w/TID equipment to QPL (12-01-10)
Addition of Outdoor Load Center for use w/TID equipment to QPL (01-25-11)
Addition of Stainless Steel NEMA 4X Enclosure; “A-2” & “B-2” required use on FDOT Projects to QPL (01-28-11)
Addition of Transient Protection Device for use w/all Service Disconnect switches to QPL (12-22-11)